Deltabar S Profibus Device Configuration
- Manufacturer View
- Operating Menu
- Settings
- Basic Setup
- Measuring Mode - Flow
- Press. Eng. Unit - inH2O
- Flow-Meas. Type - Volume operat. cond
- Unit Flow - USgal/min
- Max. Flow - Refer to specific device configuration
- Max. Press. Flow - Refer to specific device configuration
- Transmitter Info
Resetting the Device
- Manufacturer View
- Operating Menu
- Operation
- Insert Pin No
- 33333 (User Reset)
- 1 (Total Reset)
Hardware addressing
- Unscrew front cover & remove display
- Set DIP switch 8 (SW/HW) to “Off” (Down) = Hardware Addressing
- Configure the address with DIP switches 1 to 7.
- You have to wait 10 seconds for a change in address to take effect. The device is restarted.
| DIP-Switch |
1 |
2 |
3 |
4 |
5 |
6 |
7 |
| Binary Weighting |
1 |
2 |
4 |
8 |
16 |
32 |
64 |
Example
Dip-Switches 3 & 4 “On” (Up) remaining Dip-Switches “OFF”(Down)
Address = 4+8 = 12