Using the Fieldcare package on the workstation to communicate with WirelessHART devices installed on Run 4
Create Project
In the Network pane right click //Host PC// & select Add Device
Add //HART IP Communication//
In the Network pane right click //HART IP Communication// & select //Add Device//
Select WirelessHART Fieldgate / SWG70 / V1.xx click OK
Right click //HART IP Communication// & select //Additional Functions - Set DTM Addresses//
Enter 192.168.1.45 in the //UDP Address// field - Click Update changed data
In the Network pane right click WirelessHART Fieldgate & select// Create network//
Wait for the Scanning to complete
The found wireless gateways devices will appear in the //Network// pane
Right click on the required [[WirelessHART]] adaptor and select //Create network// FITWL404 to connect to [[Devices:FIT-404|FIT-404]] PITWL411 to connect to [[Devices:PIT-411|PIT-411]] PITWL410 to connect to [[Devices:PIT-410|PIT-410]]
The end device will appear under the wireless gateway
To connect to the required device, In the //Network pane// right click on the required device and select //Connect//
The Connection icon will turn from grey to green when connected
Disconnected Connected
Double click on the green connection icon
Online Parameterizewill now appear in the DTM frame
Right click the wirelss xxx Creat Network
To connect to the required device, In the //Network pane// right click on the required device and select //Connect *blur out different run **//
The Connection icon will turn from grey to green when connected
//Online Parameterize //will now appear in the DTM frame
webpage admin admin